Total cooling capacity of indoor units (kW) | Â 28.1 to 56.0 |
Fujitsu Separation Tube UTP-AX180A Application
- Dividing the variable refrigerant flow to the indoor units
- UTPAX comply with Fujitsu Airstage J-II S 2 pipe mini VRF, J-II 2-pipe mini VRF, VIII 2-pipe VRF
Fujitsu Separation Tube UTP-AX180A Features
- The separation tube obtain an liquid and gas separation tube;
- Supplied with insulation and required to use the insulation after brazing the pipe;
- There are three different types of separation tubes are available for development of the refrigerant circuit;
- Allowed installation as vertical mounting position of the separation kit;
- Max 150 as installation angle in horizontal mounting position;
- T-tubes are forbidden because it causes uneven refrigerant flow
- Minimum distance between two separation tubes or bend of 90 degree is 0,5 m in straight position. to prevent the outdoor unit malfunction and generation of refrigerant noise;
- Brazing under nitrogen is required, otherwise it will be caused to damage for compressor and clog the strainer and electronic expansion valve.
Reviews
There are no reviews yet.