The PLA-ZRP Power Inverter heat pump series offer customers high seasonal efficiency, advanced control options and quit operation, whilst providing greater flexibility and ease of installation.
|
| Heating nominal capacity (kW) | 16.0 (5.7-18.0) |
| Cooling nominal capacity (kW) | 13.4 (6.2-15.0) |
| Heating (UK) capacity (kW) | 13.6 (4.85-15.3) |
| Cooling (UK) capacity (kW) | 12.9 (5.7-14.1) |
| SHF (Nominal & UK) | 0.72 |
| COP / EER Nominal | 3.40 / 3.07 |
| SCOP / SEER (BS EN14825) | 4.5 / 6.1 |
| Heating ErP energy efficiency class | N/A |
| Cooling ErP energy efficiency class | N/A |
| Air flow (m3/min) | 24-26-29-32 |
| Gas pipe size | 5/8″ |
| Liquid pipe size | 3/8″ |
| Sound pressure level (dBA) | 36-39-42-44 |
| Sound power level (dBA) | 70 |
| Dimensions (mm) | 840 (950) x 840 (950) x 258 (35) |
| Weight Unit / Panel (kg) | 27 / 6 |
| Electrical supply Fed by | Outdoor unit |
| Fuse rating HRC (A) | 6 |
| Interconnecting cable No. cores | 4 |
| Panel reference | PLP-6BA |
| Wired remote controller reference | PAR-31MAA |
| Heating sound pressure level (dBA) | 52 |
| Cooling sound pressure level (dBA) | 50 |
| Cooling sound power level (dBA) | 70 |
| Weight (kg) | 132 |
| Dimensions (W x D x H) | 1050 x 330 + 30 x 1338 |
| Electrical supply | 220-240V, 50 Hz |
| Phase | Single |
| Nominal heating system power input (kW) | 4.70 |
| Nominal cooling system power input (kW) | 4.37 |
| Nominal UK heating system power input (kW) | 4.18 |
| Nominal UK cooling system power input (kW) | 3.71 |
| Starting Current (A) | 4.0 |
| Heating system running current (A) | 8.09 |
| Cooling system running current (A) | 7.68 |
| MAX system running current (A) | 12.1 |
| Fuse rating (BS88) (A) | 16 |
| Mains cable no cores | 5 |
| MAX pipe length (m) | 75 |
| MAX high difference (m) | 30 |
| Charge R410A (kg) | 5.0 (30m) |



Reviews
There are no reviews yet.