Mitsubishi Electric Mr Slim Power Inverter Ceiling Concealed Ducted Heat Pump offer customers high seasonal efficiency, advanced control options and quiet operation, whilst providing greater flexibility and ease of installation
|
MITSUBISHI ELECTRIC PEAD-RP140JAQ INDOOR UNIT |
|
| Heating nominal capacity | 16.0 (5.7-18.0) |
| Cooling nominal capacity | 13.4 (6.2-15.3) |
| Heating (UK) capacity | 13.6 (4.85-15.3) |
| Cooling (UK) capacity | 12.9 (5.7-14.1) |
| SHF (Nominal & UK) | 0.84 |
| COP / EER Nominal | 3.81 / 3.07 |
| SCOP / SEER (BS EN14825) | 3.6 / 4.2 |
| Heating ErP energy efficiency class | N/A |
| Cooling ErP energy efficiency class | N/A |
| Air flow (m3/min) | 32-39-46 |
| Gas pipe size | 5/8″ |
| Liquid pipe size | 3/8″ |
| External static pressure (dBA) | 35-50-70-100-150 |
| Sound pressure level (dBA) | 34-38-43 |
| Sound power level (dBA) | 66 |
| Dimensions (mm) | 1600 x 732 x 250 |
| Weight Unit | 47 |
| Electrical supply Fed by | Outdoor unit |
| Fuse rating HRC (A) | 6 |
| Interconnecting cable No. cores | 4 |
MITSUBISHI ELECTRIC PUHZ-ZRP140YKA OUTDOOR UNIT | THREE PHASE |
|
| Heating sound pressure level (dBA) | 52 |
| Cooling sound pressure level (dBA) | 50 |
| Cooling sound power level (dBA) | 70 |
| Weight (kg) | 132 |
| Dimensions (W x D x H) | 1050 x 330+30 x 1138 |
| Electrical supply | 380 -415 V, 50 Hz |
| Phase | Three |
| Nominal heating system power input (kW) | 4.20 |
| Nominal cooling system power input (kW) | 4.36 |
| Nominal UK heating system power input (kW) | 3.88 |
| Nominal UK cooling system power input (kW) | 3.57 |
| Starting Current (A) | 4.0 |
| Heating system running current (A) | 9.63 |
| Cooling system running current (A) | 9.21 |
| MAX system running current (A) | 13.8 |
| Fuse rating (BS88) (A) | 16 |
| Mains cable no cores | 5 |
| MAX pipe length (m) | 75 |
| MAX high difference (m) | 30 |
| Charge R410A (kg) | 5.0 (30 m) |