Heating nominal capacity (kW) |
6.9 (2.5-8.0) |
Cooling nominal capacity (kW) |
6.1 (2.3-6.3) |
Heating (UK) capacity (kW) |
5.87 (2.13-6.80) |
Cooling (UK) capacity (kW) |
5.61 (2.12-5.80) |
SHF (Nominal & UK) |
0.76 |
COP / EER Nominal |
3.50 / 3.32 |
SCOP / SEER (BS EN14825) |
4.1 / 6.0 |
Heating ErP energy efficiency class |
A+ |
Cooling ErP energy efficiency class |
A+ |
Air flow (m3/min) |
12-14-16-18 |
Gas pipe size |
5/8″ |
Liquid pipe size |
1/4″ |
Sound pressure level (dBA) |
28-29-31-32 |
Sound power level (dBA) |
55 |
Dimensions (mm) |
840 (950) x 840 (950) x 258 (35) |
Weight Unit / Panel (kg) |
23 / 6 |
Electrical supply Fed by |
Outdoor unit |
Fuse rating HRC (A) |
6 |
Interconnecting cable No. cores |
4 |
Panel reference |
PLP-6BA |
Wired remote controller reference |
PAR-31MAA |
Reviews
There are no reviews yet.