Key Benefits and Features Ceiling Cassette PLFY-M125VEM
|
Heating nominal capacity (kW) | 8.0 |
Cooling nominal capacity (kW) | 7.1 |
High Performance Heating UK (kW) | 8.0 |
COP Priority Heating UK (kW) | 7.5 |
Cooling UK (kW) | 6.7 |
Hi-Sensible Mode Cooling UK (kW) | 5.2 |
SHF (UK) | 0.73 |
SHF Hi – Sens Mode | 0.79 |
Heating (nominal) power input (kW) | 0.04 |
Heating (nominal) power input (kW) | 0.05 |
Air flow (Lo-Mi1-Mi2-Hi) (m3/min) | 14 – 15 – 16 – 18 |
Sound pressure level (dBA) | 28 – 29 – 30 – 32 |
Weight unit / Grille (kg) | 23 / 6 |
Unit dimensions (mm) | 840 x 840 x 258 |
Grille dimensions (mm) | 950 x 950 x 35 |
Electrical supply | 220 – 240 V, 50 Hz |
Phase | Single |
Heating running current (A) | 0.29 |
Cooling running current (A) | 0.36 |
Fuse Rating (BS88) – HRC (A) | 6 |
Mains cable No. Cores | 3 |
Panel reference | PLP-6BA |