Fujitsu AIRSTAGE V-III brings new levels of power and flexibility to large air conditioning applications. The DC Inverter based system can combine up to three outdoor units, creating virtually any configuration up to a maximum connected capacity of 150 kW with 64 indoor units. The Fujitsu Airstage V-III also uses high efficiency refrigerant, which offers superior system performance and heat transfer.
|
FUJITSU AIRSTAGE VRF AJY252LALBH 20HP AIR CONDITIONING SYSTEM AJY216LALBH MASTER | AJY090LALBH SLAVE |
Maximum Connectable Indoor Unit | 60 |
Cooling indoor unit connectable capacity | 39 – 109.5 kW |
Power Source | 3 – Phase 4 wire, 400 V 50 Hz |
Cooling Capacity | 78 kW |
Heating Capacity | 81.5 kW |
Cooling Input Power | 23.84 kW |
Heating Input Power | 20.88 kW |
Cooling EER | 3.27 W/W |
Heating COP | 3.90 W/W |
Air Flow Rate | 13,700 + 11,100 m3/h |
Cooling Sound Pressure Level | 64 dB(A) |
Heating Sound Pressure Level | 64 dB(A) |
Maximum external static pressure | 82 Pa |
Compressor motor output | 3.9 x 2 + 4.5 x 2 kW |
Heat Exchanger Fit | Blue fin |
Dimension(H x W x D) | 1690 x (930 + 1,240) x 765 mm |
Weight | 275 + 252 kg |
Refrigerant charge | 11.8 x 2 kg |
Pipe size (Gas/Liquid) | 15.88 / 34.92 mm |
Cooling Operation | -5 0C – 46 0C |
Heating Operation | -20 0C – 21 0C |
Specifications are based on the following conditions |
- Cooling: Indoor temperature of 27 0CDB / 19 0CWD, and outdoor temperature of 35 0CDB / 24 0CWD.
- Heating: Indoor temperature of 20 0CDB (15 0CWD), and outdoor temperature of 7 0CDB / 6 0CWD.
- Pipe length: 7,5 m; Height difference between outdoor unit and outdoor unit: 0 m.
- When cooling operation will be conducted at outdoor air temperature below -5 0C, the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
Reviews