MITSUBISHI ELECTRIC PEAD-RP125JAQ INDOOR UNIT
|
| Heating nominal capacity (kW) |
14.0 (5.0-16.0) |
| Cooling nominal capacity (kW) |
12.5 (5.5-14.0) |
| Heating (UK) capacity (kW) |
11.9 (4.25-13.6) |
| Cooling (UK) capacity (kW) |
11.5 (5.05-12.9) |
| SHF (Nominal & UK) |
0.84 |
| COP / EER Nominal |
3.86 / 3.09 |
| SCOP / SEER (BS EN14825) |
3.8 / 4.8 |
| Heating ErP energy efficiency class |
N/A |
| Cooling ErP energy efficiency class |
N/A |
| Air flow (m3/min) |
29.5-33.5-42 |
| Gas pipe size |
5/8″ |
| Liquid pipe size |
3/8″ |
| External static pressure (dBA) |
35 – 50 – 70 – 100 – 150 |
| Sound pressure level (dBA) |
33 – 36 – 40 |
| Sound power level (dBA) |
63 |
| Dimensions (mm) |
1400 x 732 x 250 |
| Weight Unit |
43 |
| Electrical supply Fed by |
Outdoor unit |
| Fuse rating HRC (A) |
6 |
| Interconnecting cable No. cores |
4 |
MITSUBISHI ELECTRIC PUHZ-ZRP125VKA2 OUTDOOR UNIT
|
| Heating sound pressure level (dBA) |
52 |
| Cooling sound pressure level (dBA) |
50 |
| Cooling sound power level (dBA) |
70 |
| Weight (kg) |
116 |
| Dimensions (W x D x H) |
1050 x 330+30 x 1138 |
| Electrical supply |
220-240 V, 50 Hz |
| Phase |
Single |
| Nominal heating system power input (kW) |
3.63 |
| Nominal cooling system power input (kW) |
4.05 |
| Nominal UK heating system power input (kW) |
3.60 |
| Nominal UK cooling system power input (kW) |
3.09 |
| Starting Current (A) |
12.0 |
| Heating system running current (A) |
17.95 |
| Cooling system running current (A) |
18.9 |
| MAX system running current (A) |
29.3 |
| Fuse rating (BS88) (A) |
32 |
| Mains cable no cores |
3 |
| MAX pipe length (m) |
75 |
| MAX high difference (m) |
30 |
| Charge R410A (kg) |
5.0 (30 m) |
Reviews