Fujitsu energy recovery ventilator is silence extremely high efficiency and low noise levels are achieved by using a highly efficient heat exchange process. A comfortable air conditioned space is achieved by conveniently selecting whether to use heat exchange or normal ventilation setting, according to the requirements of the conditioning space at commercial premisses.
Recovery Ventilator Key Features:
|
In order to use a Fujitsu hard-wired controller with the ERV units an interface is required to communicated between energy recovery ventilator and hard wire controller
UTY-ERV2 Interface Key Features:
- UTI-ERV2 interface is supplied with an outside air intake duct sensor for control of the ERV bypass damper e.g. heat recovery or free cooling mode;
- Available dry contact terminals for remote control On/Off from Building Management System (BMS);
- Allows the use of Fujitsu UTY-RNNYM hard wired controller which has the following features: fan speed selection, 7 day programmable clock, temperature selection option for auto control of the damper, filter clean indicator, Manual or Auto Energy Recovery Ventilator Control Of bypass damper
Power source | 220 – 240 V, 50 Hz |
H.E.V.* Input power | 418 / 378 / 295 W |
H.E.V. Air flow rate | 800 / 800 / 630 m3/h |
H.E.V. External static pressure | 140 / 110 / 55 Pa |
H.E.V. Temperature exchange efficiency | 75 / 75 / 76 % |
H.E.V. Energy exchange efficiency cooling | 65 / 65 / 66 % |
H.E.V. Energy exchange efficiency heat pump | 71 / 71 / 68 % |
H.E.V. Sound pressure level | 37.5 / 37.5 / 34.5 dB |
N.V.** Input power | 418 / 378 / 295 W |
N.V. Air flow rate | 800 / 800 / 630 m3/h |
N.V. External static pressure | 140 / 110 / 55 Pa |
N.V. Sound pressure level | 37.5 / 37.5 / 34.5 dB |
Dimensions (h × w × d) | 1322 x 884 x 388 mm |
Recommended fuse | 6 A |
Weight | 71 kg |
Outlet duct diameter | 250 mm |
Operation range | – 10 to 40 0C |
Maximum humidity | 85 % |
H.E.V. * – Heat Exchange Ventilation
N.V. ** – Normal Ventilation
Reviews
There are no reviews yet.