| MITSUBISHI ELECTRIC PEAD-RP50JAQ INDOOR UNIT |
| Heating nominal capacity (kW) |
6.0 (2.5-7.3) |
| Cooling nominal capacity (kW) |
5.0 (2.3-5.6) |
| Heating (UK) capacity (kW) |
5.1 (2.15-6.2) |
| Cooling (UK) capacity (kW) |
4.6 (2.1-5.15) |
| SHF (Nominal & UK) |
0.84 |
| COP / EER Nominal |
4.00 / 3.47 |
| SCOP / SEER (BS EN14825) |
4.3 / 5.5 |
| Heating ErP energy efficiency class |
A+ |
| Cooling ErP energy efficiency class |
A |
| Air flow (m3/min) |
12 – 14.5 – 17 |
| Gas pipe size |
1/2″ |
| Liquid pipe size |
1/4″ |
| External static pressure (dBA) |
35 – 50 – 70 – 100 – 150 |
| Sound pressure level (dBA) |
26-31-35 |
| Sound power level (dBA) |
57 |
| Dimensions (mm) |
900 x 732 x 250 |
| Weight Unit |
28 |
| Electrical supply Fed by |
Outdoor unit |
| Fuse rating HRC (A) |
6 |
| Interconnecting cable No. cores |
4 |
| MITSUBISHI ELECTRIC PUHZ-ZRP50VKA OUTDOOR UNIT |
| Heating sound pressure level (dBA) |
46 |
| Cooling sound pressure level (dBA) |
44 |
| Cooling sound power level (dBA) |
65 |
| Weight (kg) |
46 |
| Dimensions (W x D x H) |
809 x 300 x 630 |
| Electrical supply |
220-240 V, 50 Hz |
| Phase |
Single |
| Nominal heating system power input (kW) |
1.5 |
| Nominal cooling system power input (kW) |
1.44 |
| Nominal UK heating system power input (kW) |
1.28 |
| Nominal UK cooling system power input (kW) |
1.28 |
| Starting Current (A) |
5.0 |
| Heating system running current (A) |
7.65 |
| Cooling system running current (A) |
7.09 |
| MAX system running current (A) |
14.4 |
| Fuse rating (BS88) (A) |
16 |
| Mains cable no cores |
3 |
| MAX pipe length (m) |
50 |
| MAX high difference (m) |
30 |
| Charge R410A (kg) |
2.4 (30 m) |
Reviews