Rated Airflow |
7500 m3/h |
Airflow range |
5500 – 7500 m3/h |
Max Static Pressure (Factory settings) |
250 Pa |
Max Static Pressure Configuration Option |
400 Pa |
Coil Capacity Cooling (Rated) |
26.6 kW |
Recovery Module Capacity Cooling Rated |
22.9 kW |
Total Capacity |
49.5 kW |
Coil Capacity Heating (Rated) |
31.5 kW |
Recovery Module Capacity Heating Rated |
54. 4 kW |
Total Capacity |
85.9 kW |
Sensible Heat Recovery Efficiency |
72 % |
Total Heat Recovery Efficiency Cooling |
62 % |
Total Heat Recovery Efficiency Heating |
67 % |
Number of Lossnay Heat Recovery Modules |
6 |
Supply fans Power Input / 250 Pa |
2.9 / 3.1 kW |
Return fans Power Input / 250 Pa |
1.6 / 2.7 kW |
Auxiliary Transformer |
0.15 kW |
Total Power Input |
4.65 / 5.95 kW |
COP / EER (Rated) |
7.88 / 4.63 |
Filter Section |
Rigid Pocket , F7 Class (EU7) |
Outdoor Unit |
PUHZ-ZRP250YKA |
Monoblock Dimensions (WxDxH) |
4450 x 1870 x 2300 mm |
6 Section Dimensions (WxDxH) |
4850 x 1870 x 2430 mm |
Monoblock Weight |
2380 kg |
6 Section Dimensions Weight |
2650 kg |
Outdoor Unit Dimensions |
1050 x 330 +30 x 1338 mm |
Outdoor Unit Weight |
141 kg |
Electric Pre-Heating Coil |
12 kW |