Rated Airflow |
5000 m3/h |
Airflow range |
3500 – 5000 m3/h |
Max Static Pressure (Factory settings) |
250 Pa |
Max Static Pressure Configuration Option |
400 Pa |
Coil Capacity Cooling (Rated) |
21.3kW |
Recovery Module Capacity Cooling Rated |
15.3 kW |
Total Capacity |
36.6 kW |
Coil Capacity Heating (Rated) |
25.0 kW |
Recovery Module Capacity Heating Rated |
36.6 kW |
Total Capacity |
61.3 kW |
Sensible Heat Recovery Efficiency |
72 % |
Total Heat Recovery Efficiency Cooling |
62 % |
Total Heat Recovery Efficiency Heating |
67 % |
Number of Lossnay Heat Recovery Modules |
4 |
Supply fans Power Input / 250 Pa |
2.1 / 2.7 kW |
Return fans Power Input / 250 Pa |
1.6 / 2.7 kW |
Auxiliary Transformer |
0.15 kW |
Total Power Input |
3.85 / 5.55 kW |
COP / EER (Rated) |
7.01 / 4.23 |
Filter Section |
Rigid Pocket , F7 Class (EU7) |
Outdoor Unit |
PUHZ-ZRP200YKA |
Monoblock Dimensions (WxDxH) |
4450 x 1200 x 2300 mm |
6 Section Dimensions (WxDxH) |
4870 x 1200 x 2300 mm |
Monoblock Weight |
1950 kg |
6 Section Dimensions Weight |
2150 kg |
Outdoor Unit Dimensions |
1050 x 330 +30 x 1338 mm |
Outdoor Unit Weight |
141 kg |
Electric Pre-Heating Coil |
8 kW |
Reviews
There are no reviews yet.