| FUJITSU AIRSTAGE ARXC96GATH INDOOR UNIT |
| Power Source | Single Phase, 230 V ~ 50 Hz |
| UK Total Cooling Capacity | 20.8 kW |
| UK Sensible Cooling Capacity | 16.7 kW |
| UK Heating Capacity | 29.3 kW |
| Nominal Cooling Capacity | 28.0 kW |
| Nominal Heating Capacity | 31.5 kW |
| Input Power | 838 W |
| High Airflow Rate | 4850 m3/h |
| Med Airflow Rate | 4250 m3/h |
| Low Airflow Rate | 3600 m3/h |
| Sound Pressure | 0 to 300 Pa |
| Standard Static Pressure | 150 Pa |
| High Sound Pressure Level | 48 dB(A) |
| Med Sound Pressure Level | 45 dB(A) |
| Low Sound Pressure Level | 42 dB(A) |
| Net Dimension | 550 x 15870 x 700 mm |
| Weight | 105 kg |
| Pipe size (Liquid & Gas) | 1/2″ & 7/8″ inches |
| SPECIFICATIONS ARE BASED FOR ALL FUJITSU VRF INDOOR UNITS |
- Nominal Cooling: Indoor temperature of 27 0CDB / 19 0CDB and outdoor temperature of 35 0CDB / 24 0CDB
- Nominal Heating: Indoor temperature of 20 0CDB and outdoor temperature of 7 0CDB
- UK Cooling: Indoor temperature of 23 0CDB / 16 0CDB and outdoor temperature of 30 0CDB
- UK Heating: Indoor temperature of 20 0CDB and outdoor temperature of 0 0CDB